Download Print this page

YASKAWA E-II SGM H Series User Manual page 61

Advertisement

Wiring
3.4.4 Interface Circuits
3
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
D Connecting to an Open-collector Output Circuit
Alarm code signals are output from open-collector transistor output circuits.
Connect an open-collector output circuit through a photocoupler, relay or line receiver cir-
cuit.
5 to 12 VDC
Servopack
end
P
0 V
0 V
5 to 12 VDC
Servopack
end
P
0 V
D Connecting to a Photocoupler Output Circuit
Photocoupler output circuits are used for servo alarm, servo ready, and other sequence out-
put signal circuits.
Connect a photocoupler output circuit through a relay or line receiver circuit.
5 to 24 VDC
Servopack
end
Note
The maximum allowable voltage and current capacities for photocoupler output
circuits are as follows.
·Voltage: 30 VDC max.
·Current: 50 mA DC max.
Photocoupler
Servopack
end
Note
The maximum allowable voltage and current capaci-
0 V
ties for open-collector output circuits are as follows.
·Voltage: 30 VDC max.
·Current: 20 mA DC max.
Relay
Servopack
end
0 V
3 -26
5 to 24 VDC
Relay
0 V
5 to 12 VDC
P
0 V