YASKAWA E-II SGM H Series User Manual page 156

Advertisement

User Constant Settings and Functions
5.5.1 Using Servo Alarm and Alarm Code Outputs
5.5 Forming a Protective Sequence
5.5.1 Using Servo Alarm and Alarm Code Outputs
5
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
This section describes the procedure for using I/O signals from the Servopack to form a protective
safety sequence.
The basic procedure for connecting alarm output signals is described below.
Photocoupler output
(per output )
Maximum operating voltage:
30 VDC
Maximum output current: 50 mA
DC
Open collector output
(per output)
Maximum operating voltage:
30 VDC
Maximum output current: 50 mA
DC
A suitable external I/O power supply must be provided by the user separately because there is
no internal 24-V power supply in the Servopack.
The use of the photocoupler output signals is described below.
Output ® ALM+ CN1-31
Output ® ALM-- CN1-32
These alarms are output when a Servopack alarm is detected.
Servopack
Alarm
ALM output
detection
Turns power OFF.
Form an external circuit so this alarm output (ALM) turns the Servopack OFF.
ON:
Circuit between CN1-31 and 32 is closed,
and CN1-31 is at low level.
OFF: Circuit between CN1-31 and 32 is open, and
CN1-31 is at high level.
Servopack
Photocoupler
CN1-31
50 mA max.
CN1-32
CN1-37
20 mA max.
CN1-38
CN1-39
CN1-1
0 V
Servo Alarm Output
Signal Ground for Servo Alarm
Output
Normal state
Alarm state
5 -68
I/O power supply
+24 V
ALM+
ALM- -
ALO1
ALO2
ALO3
SG
0 V
Host controller
Speed/Torque
Control,
Position Control
Speed/Torque
Control,
Position Control
0 V