M‐Thermal Split
 
3.3 Startup Control for Heating and Domestic Hot Water Operation 
Table 3‐3.1: Component control during startup in heating and domestic hot water modes 
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
Notes: 
1.
Refer to Figure 3‐3.1, Figure 3‐3.2 in Part 3, 3.2 "Compressor Startup Program".
2.
Refer to Table 3‐4.1 in Part 3, 4.6 "Outdoor Fan Control".
 
3.4 Startup Control for Cooling Operation 
Table 3‐3.2: Component control during startup in cooling mode 
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
 
4 Normal Operation Control 
4.1 Component Control during Normal Operation 
Table 3‐4.1: Component control during heating and domestic hot water operations 
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
 
 
18                                                                                                                                                                                                                      201909 
Wiring diagram 
label 
COMP 
FAN 
EXV 
4‐WAY 
 
Wiring diagram 
label 
COMP 
FAN 
EXV 
4‐WAY 
Wiring diagram 
label 
COMP 
FAN 
EXV 
4‐WAY 
 
Midea CAC Confidential
 
4‐10kW 
Control functions and states 
Compressor  startup  program  selected  according  to 
● 
ambient temperature
Fan run at maximum speed
● 
Position  (steps)  from  0  (fully  closed)  to  480  (fully  open), 
controlled  according  to  outdoor  ambient  temperature, 
● 
discharge  temperature,  suction  superheat,  compressor 
speed and refrigerant system pressure 
On 
● 
 
4‐10kW 
Control functions and states 
Compressor  startup  program  selected  according  to 
● 
ambient temperature
Fan run at maximum speed
● 
Position  (steps)  from  0  (fully  closed)  to  480  (fully  open), 
controlled  according  to  outdoor  ambient  temperature, 
● 
discharge  temperature,  suction  superheat,  compressor 
speed and refrigerant system pressure 
Off 
● 
Control functions and states 
4‐10kW 
Controlled  according  to  load  requirement  from  hydronic 
● 
system 
Controlled  according  to  outdoor  heat  exchanger  pipe 
● 
temperature   
Position  (steps)  from  0  (fully  closed)  to  480  (fully  open), 
controlled  according  to  outdoor  ambient  temperature, 
● 
discharge  temperature,  suction  superheat,  compressor 
speed and refrigerant system pressure 
On 
● 
1
 
2
 
1
 
2
 
 