M‐Thermal Split
 
4.14 P0, HP Troubleshooting 
Digital display output 
       
 
Description 
 P0  indicates  suction  pipe  low  pressure  protection.  When  the  suction  pressure  falls  below  0.14MPa,  the  system 
displays P0 protection and M‐Thermal Split stops running. When the pressure rises above 0.3MPa, P0 is removed and 
normal operation resumes. 
 HP indicates P0 protection has occurred 3 times in 60 minutes. When an HP error occurs, a manual system restart is 
required before the system can resume operation. 
 Error code is displayed on outdoor unit main PCB and user interface. 
 
Possible causes 
 Low pressure switch not connected properly or has malfunctioned. 
 Insufficient refrigerant. 
 Low pressure side blockage. 
 Poor evaporator heat exchange in heating mode or DHW mode. 
 Insufficient water flow in cooling mode. 
 Outdoor unit main PCB damaged. 
 
 
 