M‐Thermal Split
 
2.5 DIP switch setting and wire connecting for Modbus function 
The  rotating coded switch S3(0‐F)  on  the  main  control  board  of  hydraulic  module   is  used  for  setting  the  modbus 
address. By default the units have this coded switch positioned=0, but this corresponds to the modbus address 16, while 
the others positions corresponds the number, e.g. pos=2 is address 2, pos=5 is address 5. 
 
Figure 4‐2.4: Rotating switch     
 
 
Figure 4‐2.5: Connection
 
Hydronic box
 
Figure 4‐2.6: Wiring
 
1
A
A
38 
Wired controller
5E
E
4Y
Y
3X
X
2B
B
1A
A
5E
E
4Y
Y
3X
X
2B
B
1A
A
.
.
.
.
.
.
XT6
2
3
4
5
B
X
Y
E
B
X
Y
E
H2
Wired Controller
H1
Midea CAC Confidential
 
A+ B- E
H1 H2
H1 H2
Max. 16 units
Input Voltage(A/B)
Wiring size 
 
E
A+
Modlous
B-
Modbus
Modbus
BMS
13.5VAC
 
 
0.75mm²
 
   
 
201909 