Hydronic system SW4 check button 
Button SW4 is used to check the parameters of the hydronic system. Refer to Table 4‐2.1. First, press Button SW4 for 3 
seconds and the first parameter (operating mode) will be displayed. Then, on each subsequent press, the next parameter 
is displayed. 
Table 4‐2.5: SW4 system check 
Number  Parameters displayed on digital display 
Mode 
Capacity Requirements 
Capacity Requirements (Correct) 
T1: Backup electric heater exchanger water outlet temperature 
T1B: Leaving water temperature of region 2 
T1S:  Target  leaving  water  temperature  of  region  1  calculated 
from climate‐related curves (°C) 
T1S2:  Target  leaving  water  temperature  of  region  2  calculated 
from climate‐related curves (°C) 
Ta: Room temperature (°C) 
:
T5
DHW tank temperature (°C) 
:
T2
Water  side  heat  exchanger  refrigerant  inlet  (liquid  pipe) 
10 
temperature 
:
T2B
Water  side  heat  exchanger  refrigerant  outlet  (gas  pipe) 
11 
temperature 
Tw_out:  Water  side  heat  exchanger  water  outlet  temperature 
12 
(°C) 
13 
Tw_in: Water side heat exchanger water inlet temperature (°C) 
:
14 
T4
 Outdoor ambient temperature (°C)   
15 
Current (Reserved) 
16 
Current (Reserved) 
17 
Last failure 
18 
Last second failure 
19 
Last third failure 
20 
Software version 
21 
‐‐ 
Digital Display Output 
Table 4‐2.6: Digital display output in different operating states
M‐Thermal Split system state 
On standby 
Normal operation 
Error or protection   
System check   
201909                                                                                                                                                                                                                        37 
 
 
Parameters displayed on outdoor 
unit main PCB DSP1 
Running  speed  of  the  compressor  in 
rotations per second 
Error or protection code 
Refer to Table 4‐2.4 
Midea CAC Confidential
 
Remarks 
0: off; 2: cooling; 3: heating; 5: DHW. 
Actual value = value displayed
Actual value = value displayed
When no decimal point is displayed: 
Temperature is ≥ ‐9°C, Actual value = value displayed
When decimal point is displayed between the two digits: 
Temperature is ≤ ‐10°C, Actual value = value displayed x ‐10
Example: "1.2" indicates ‐12°C
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed (If Ta is used)
When no decimal point is displayed: 
Temperature is ≥ ‐9°C, Actual value = value displayed
When decimal point is displayed between the two digits: 
Temperature is ≤ ‐10°C, Actual value = value displayed x ‐10
Example: "1.2" indicates ‐12°C
‐‐ 
‐‐ 
"‐‐" is displayed if no error or protection events have occurred 
 
since start‐up
"‐‐" is displayed if no error or protection events have occurred 
 
since start‐up
"‐‐" is displayed if no error or protection events have occurred 
 
since start‐up
Version number 
 
Parameters displayed on hydronic 
box main PCB DSP1 
Leaving water temperature (°C) 
Error or protection code   
Refer to Table 4‐2.5 
  M‐Thermal Split
 
 
 
 
 
 
 
 