M‐Thermal Split
 
2.4 Check Buttons 
Refrigerant system SW2 check button 
Button SW2 is used to check the parameters of the refrigerant system. Refer to Table 4‐2.2 First, press Button SW2 for 3 
seconds and the first parameter (operating mode) will be displayed. Then, on each subsequent press, the next parameter 
is displayed. 
 
Table 4‐2.4: SW2 system check 
Number  Parameters displayed on digital display 
Mode 
Fan speed   
Capacity requirements 
Capacity requirements(Correct) 
Frequency limit code 
T3: Condenser temperature (°C) 
T4: Outdoor ambient temperature (°C) 
Tp: Discharge temperature (°C)       
Th: Suction temperature (°C) 
10 
TF: Radiator temperature (°C) 
11 
Electric Expansive Valve 
12 
Actual current 
13 
Compressor current 
14 
Voltage AC 
15 
Voltage DC
 
16 
Pressure
17 
Software version 
18 
Last fault 
19 
‐‐ 
36 
 
Remarks 
0: standby; 2: cooling; 3: heating; 4 forced cooling. 
The fan speed index is related to the fan speed in rpm as described in Table 3‐4.1 in Part 3, 4.6 
 
"Outdoor Fan Control".
Compressor frequency 
Compressor frequency 
0: Without restriction 
1: Compressor frequency restriction by o
2: 
Compressor frequency restriction by c
3: 
Compressor frequency restriction by actual c
4: 
Compressor frequency restriction by 
5:
 Compressor frequency restriction by 
6: 
Compressor frequency restriction by
7: 
Compressor frequency restriction by pressure 
When no decimal point is displayed: 
Temperature is ≥ ‐9°C 
Actual value = value displayed
When decimal point is displayed between the two digits: 
Temperature is ≤ ‐10°C 
Actual value = value displayed x ‐10 
Example: "1.2" indicates ‐12°C 
When  the  temperature  <  100  °C,  actual  value  =  value  displayed.  When  the 
temperature  ≥  100 °C, actual value = value displayed × 10 
When no decimal point is displayed: 
Temperature is ≥ ‐9°C 
Actual value = value displayed
When decimal point is displayed between the two digits: 
Temperature is ≤ ‐10°C 
Actual value = value displayed x ‐10 
Example: "1.2" indicates ‐12°C 
Actual value = value displayed 
Steps = value displayed × 8 
Actual value = value displayed 
Actual value = value displayed 
Actual value = value displayed × 10 
Actual value = value displayed × 10 
Actual value = value displayed 
Version number 
"nn" is displayed if no error or protection events have occurred since start‐up 
 
Midea CAC Confidential
utdoor ambient temperature 
ondenser temperature 
urrent 
voltage AC 
radiator temperature 
 Discharge temperature 
   
201909 