M‐Thermal Split
 
4.15 P1 Troubleshooting 
Digital display output 
 
 
Description 
 Discharge  pipe  high  pressure  protection.  When  the  discharge  pressure  rises  above  4.2MPa,  the  system  displays  P1 
protection and M‐Thermal Split stops running. When the discharge pressure falls below 3.2MPa, P1 is removed and 
normal operation resumes.   
 Error code is displayed on outdoor unit main PCB and user interface. 
 
Possible causes 
 Pressure sensor/switch not connected properly or has malfunctioned. 
 Excess refrigerant. 
 System contains air or nitrogen. 
 High pressure side blockage. 
 Poor condenser heat exchange. 
 Outdoor unit main PCB damaged. 
 