Procedure 
 
Air side heat exchanger refrigerant outlet 
temperature sensor is loose
Air side heat exchanger refrigerant outlet 
temperature sensor has short‐circuited 
The air side heat exchanger heat 
exchange is poor
The fan or fan motor is blocked or 
Replace outdoor main PCB 
 
Notes:   
1.
Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connection port are CN9 on the outdoor unit main 
PCB ( labeled 12 in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System, Inverter Module").. 
2.
Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short‐circuited.  If  the  resistance  is  not  consistent  with  the  sensor's  resistance 
characteristics table, the sensor has failed. Refer to Part 2, 1.1 "Outdoor Unit Layout" and to Table 4‐5.1 in Part 4, 5.1 "Temperature  Sensor Resistance 
Characteristics". 
3.
Check air side heat exchanger, fan and air outlets for dirt/blockages. 
 
201909                                                                                                                                                                                                                        79 
Pd 
     
1
 
    No 
2
or failed
 
    No 
3
 
    No 
damaged 
    No 
 
Midea CAC Confidential
 
 
 
Ensure the temperature sensor is 
Yes 
connected properly 
 
Yes 
Replace the temperature sensor 
 
Yes 
Inspect the system and fix the error 
 
Yes 
Inspect the system and fix the error 
 
 
  M‐Thermal Split
 
 
 
 
 
 
 
 