M‐Thermal Split
 
Table 3‐6.4: Component control during force cool operation 
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
 
6.4 Fast DHW Operation 
Fast DHW operation is used to quickly meet a requirement for domestic hot water when DHW priority has been set on the 
user interface. Refer to the M‐Thermal Split Engineering Data Book Part 3, 8.4 "DHW MODE SETTING Menu". 
 
Table 3‐6.5: Component control during fast DHW operation 
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
Tank electric heater 
 
6.5 Two zones control
Two zones control function is used to control temperature of each zone separately, thus different type radiator will operate 
at its optimal temperature and water pump cycle time will be reduced to save energy. 
 
In two zones control for cooling mode, when the setting temperature of a certain zones is reached, the zone and water 
pump of this zone will turn off. 
 
In two zones control for heating mode, the on/off control of zone and water pump is same with cooling mode, but in 
addition, the mixing valve (3‐way valve SV3) control function will be activated to adjust the water temperature of the low 
temperature zone by control the opening time and closing time of the valve. The mixing valve will only turn on when two 
zones control for heating is activated. On other conditions, the mixing valve will keep off. 
 
When the valve initially turns on, the opening time and closing time is same and then the time is controlled according to 
the difference between water pipe temperature and setting water temperature of the controlling zone.   
 
Note: 
1.
M‐Thermal units just have the controlling function, while the mixing valve, water pump of each zone need to be field 
supplied and connect to M‐Thermal unit. 
 
24                                                                                                                                                                                                                      201909 
Wiring diagram 
label 
COMP 
FAN 
EXV 
4‐WAY 
Wiring diagram 
label 
COMP 
FAN 
EXV 
4‐WAY 
TBH 
1
 
 
Midea CAC Confidential
 
Control functions and states 
4‐10kW 
Runs at force cooling operation rotation speed 
● 
Runs at force cooling operation speed 
● 
304 (steps) 
● 
Off 
● 
Control functions and states 
4‐10kW 
Controlled according to load requirement 
● 
Controlled  according  to  outdoor  heat  exchanger  pipe 
● 
temperature 
Position  (steps)  from  0  (fully  closed)  to  480  (fully  open), 
● 
controlled according to discharge superheat 
On 
● 
On 
● 
 