4.6 EE Troubleshooting
Digital display output
Description
Hydronic box main PCB EEPROM error.
M‐Thermal Split stops running.
Error code is displayed on hydronic box main PCB and user interface.
Possible causes
Hydronic box main PCB EEPROM is not connected properly.
Hydronic box main PCB damaged.
Procedure
Hydronic box main PCB EEPROM
connected properly
Replace hydronic box main PCB
Notes:
1.
Hydronic box main PCB EEPROM is designated IC18 on the main PCB for hydronic box (labeled 32 in Figure 4‐2.1 in Part4, 2.2 "Main PCB for Hydronic
System").
50
EE
1
is not
No
Midea CAC Confidential
Ensure the EEPROM is connected
Yes
properly