Normal Operation Control - Midea MV5-X252W/V2GN1 Service Manual

Commercial air conditioners
Table of Contents

Advertisement

5 Normal Operation Control

5.1 Component Control During Normal Operation
Table 3-5.1: Component control during normal cooling operation
Component
Inverter compressor A
Inverter compressor B
DC fan motor A
DC fan motor B
Electronic expansion valve A
Electronic expansion valve B
Four-way valve
Solenoid valve (liquid refrigerant injection)
Solenoid valve (oil balance)
Solenoid valve (fast defrosting)
Solenoid valve (EXV bypass)
Solenoid valve (indoor units bypass)
Table 3-5.2: Component control during heating operation
Component
Inverter compressor A
Inverter compressor B
DC fan motor A
DC fan motor B
Electronic expansion valve A
Electronic expansion valve B
Four-way valve
Solenoid valve (liquid refrigerant injection)
Solenoid valve (oil balance)
Solenoid valve (fast defrosting)
Solenoid valve (EXV bypass)
Solenoid valve (indoor units bypass)
5.2 Compressor Output Control
The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor
units first estimate the indoor unit load requirement according to the nominal capacity of indoor units currently running,
and then correct for ambient temperature. The compressors then start up according to the corrected load requirement.
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures. If the actual load requirement can be provided by one unit alone, then only
one unit starts up. If the actual load requirement requires all outdoor unit modules to operate, the weighted average
actual load requirement is sent to each module and each module operates according to this distributed load
requirement.
201608
Wiring
8-12HP
14-22HP
diagram label
COMP(INV)
COMP(INV1)
FANA
FANB
EXVA
EXVB
ST1
SV2
SV4
SV5
SV6
SV7
Wiring
8-12HP
14-22HP
diagram label
COMP(INV)
COMP(INV1)
FANA
FANB
EXVA
EXVB
ST1
SV2
SV4
SV5
SV6
SV7
Control functions and states
Controlled according to load requirement
Controlled according to discharge pressure
Position (steps) from 0 (fully closed) to 480 (fully
open),
controlled
temperature
Off
Only open if discharge temperature > 100
Open regularly
Off
Only open if pressure > 3.6MPa
Controlled according to load requirement
Control functions and states
Controlled according to load requirement
Controlled according to outdoor heat exchanger pipe
temperature
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge superheat
On
Only open if discharge temperature > 100
Open regularly
Open during defrosting operation
Off
Controlled according to load requirement