Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
Pressure sensor not connected properly or has malfunctioned.
Outdoor unit main PCB is damaged.
Procedure
High pressure sensor connection on
outdoor unit main PCB is loose
High pressure sensor has short‐circuited
Replace outdoor unit main PCB
Notes:
1.
Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed. The pressure sensor connection on each type of outdoor unit main PCB is labeled in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System,