4.13 H8 Troubleshooting 
Digital display output 
 
 
Description 
 Pressure sensor error. 
 M‐Thermal Split stops running. 
 Error code is displayed on outdoor unit main PCB and user interface. 
 
Possible causes 
 Pressure sensor not connected properly or has malfunctioned. 
 Outdoor unit main PCB is damaged. 
 
Procedure 
 
High pressure sensor connection on 
outdoor unit main PCB is loose 
High pressure sensor has short‐circuited 
Replace outdoor unit main PCB 
 
Notes:   
1.
Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor 
has failed. The pressure sensor connection on each type of outdoor unit main PCB is labeled in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System, 
Inverter Module". 
 
201909                                                                                                                                                                                                                        59 
H8 
    No 
    No 
1
or failed
 
    No 
 
Midea CAC Confidential
 
 
 
Yes 
Ensure the sensor is connected properly
 
Yes 
Replace the sensor 
 
 
  M‐Thermal Split
 
 
 
 
 
 