Procedure 
 
E5 / E6 / E9 / EA 
Temperature sensor connection on 
outdoor unit main PCB is loose
Temperature sensor has short‐circuited 
Replace outdoor unit main PCB 
 
Notes:   
1.
Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature  sensor connections are port CN9  on the outdoor unit 
main PCB (labeled 12 in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System, Inverter Module". Discharge pipe temperature sensor connection is 
port CN8 on the refrigerant system main PCBs (labeled 11 in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System, Inverter Module"). Suction pipe 
temperature sensor connection is port CN1 on the main control board (labeled 13 in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant System, Inverter 
Module").   
2.
Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short‐circuited.  If  the  resistance  is  not  consistent  with  the  sensor's  resistance 
characteristics table, the sensor has failed. Refer to Table 4‐5.1, and Table 4‐5.2 in Part 4, 5.1 "Temperature Sensor Resistance Characteristics". 
 
 
201909                                                                                                                                                                                                                        49 
     
1
 
    No 
2
or failed
 
    No 
 
Midea CAC Confidential
 
 
 
Yes 
Ensure the sensor is connected properly
 
Yes 
Replace the sensor 
 
 
  M‐Thermal Split
 
 
 
 
 
 