Procedure 
 
Water side heat exchanger water inlet / 
outlet temperature sensor is loose
Water side heat exchanger water inlet / 
outlet temperature sensor has 
short‐circuited or failed
The 4‐way valve is blocked or damaged
Replace outdoor main PCB 
 
Notes:   
1.
water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on 
the hydronic box main PCB (labeled 11 in Figure 4‐2.1 in Part4, 2.2 "Main PCB for Hydronic System"). 
2.
Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short‐circuited.  If  the  resistance  is  not  consistent  with  the  sensor's  resistance 
characteristics  table,  the  sensor  has  failed.  Refer  to  Part  2,  1.2  "Hydronic  Box  Layout"  and  to  Table  4‐5.1  to  4‐5.2  in  Part  4,  5.1  "Temperature  Sensor 
Resistance Characteristics". 
3.
Restart the unit in cooling mode to change the refrigerant flow direction. If the unit does not operate normally, the 4‐way valve is blocked or damaged. 
 
 