6 Special Control 
6.1 Oil Return Operation 
In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil that has 
flowed  out  of  the  compressor  and  into  the  refrigerant  piping.  When  the  oil  return  operation  is  being  conducted,  the 
outdoor unit refrigerant system main PCB displays code d0. 
 
The oil return operation starts when the following condition occurs: 
 When the compressor cumulative operating time with running rotation speed less than 42rps reaches 6 hours. 
 
The oil return operation ceases when any one of the following three conditions occurs: 
 Oil return operation duration reaches 5 minutes. 
 Compressor stops. 
 
Tables 3‐6.1 show component control during oil return operation in cooling mode. 
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
 
Tables 3‐6.2 show component control during oil return operation in heating and DHW modes. 
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
 
6.2 Defrosting Operation 
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit air side heat exchanger 
is performing as a condenser. The defrosting operation is controlled according to outdoor ambient temperature, air side 
heat exchanger refrigerant outlet temperature and the compressor running time. 
 
Table 3‐6.3: Component control during defrosting operation   
Component 
Inverter compressor   
DC fan motor 
Electronic expansion valve   
Four‐way valve 
 
6.3 Force Cooling Operation 
The force cooling operation helps the refrigerant recovering before removal the water side heat exchanger.   
 
The force cool mode can be ended by pushing the button on the outdoor refrigerant system main PCB named "force‐cool" 
for 5s or this mode will be ended automatic if the system has operated force cool mode for more than 30 minutes. 
 
201909                                                                                                                                                                                                                      23 
 
Wiring diagram 
4‐10kW 
label 
COMP 
● 
FAN 
● 
EXV 
● 
4‐WAY 
● 
Wiring diagram 
4‐10kW 
label 
COMP 
● 
FAN 
● 
EXV 
● 
4‐WAY 
● 
Wiring diagram 
4‐10kW 
label 
COMP 
● 
FAN 
● 
EXV 
● 
4‐WAY 
● 
Midea CAC Confidential
  M‐Thermal Split
Control functions and states 
Runs at oil return operation rotation speed 
Controlled according to cooling mode 
304 (steps) 
Off 
Control functions and states 
Runs at oil return operation rotation speed 
Controlled according to heating mode 
304 (steps) 
On 
Control functions and states 
Runs at defrosting operation rotation speed 
Off 
Fully open 
Off 
 

Hide quick links:

Advertisement

loading