M‐Thermal Split
 
Procedure 
 
Water side heat exchanger water inlet / 
outlet temperature sensor is loose
Water side heat exchanger water inlet / 
outlet temperature sensor has 
short‐circuited or failed
Water piping contains air 
The water flow rate is not sufficient, 
caused by crushed or bent water piping, 
incorrect pump speed setting, high 
resistance in water piping or broken 
expansion vessel
Replace hydronic box main PCB 
 
Notes:   
1.
Water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on 
the hydronic box main PCB (labeled11 in Figure 4‐2.1 in Part4, 2.2 "Main PCB for Hydronic System"). 
2.
Measure  sensor  resistance.  If  the  resistance  is  too  low,  the  sensor  has  short‐circuited.  If  the  resistance  is  not  consistent  with  the  sensor's  resistance 
characteristics table, the sensor has failed. Refer to Part 2,  1.2 "Hydronic Box Layout" and to Table 5‐5.3 in Part 5,  5.1 "Temperature Sensor Resistance 
Characteristics". 
3.
Refer to the M‐Thermal Split Engineering Data Book, Part 5, 15 "SPECIAL FUNCTIONS". 
4.
Check  water  pressure  on  the  manometer.  If  the  water  pressure  is  not  >  1  bar,  water  flow  is  insufficient.  Refer  to  Figures  2‐1.7  and  2‐1.8  in  Part  2,  1.2 
"Hydronic Box Layout". 
 
 
70 
P5 
     
1
 
    No 
2
 
    No 
    No 
4
 
    No 
 
Midea CAC Confidential
 
 
 
Ensure the temperature sensor is 
Yes 
connected properly 
 
Yes 
Replace the temperature sensor 
 
Yes 
Purge air from the water system
 
Yes 
Inspect the system and fix the error 
 
 
 
 
 
 
2
 
 
 
 
   
201909 