4.18 P5 Troubleshooting 
Digital display output 
   
 
Description 
 High  temperature  difference  between  water  side  heat  exchanger  water  inlet  and  water  outlet  temperatures 
protection. 
 M‐Thermal Split stops running. 
 Error code is displayed on hydronic box main PCB and user interface. 
 
Possible causes 
 Temperature sensor not connected properly or has malfunctioned. 
 Water piping contains air. 
 Insufficient water flow. 
 Hydronic box main PCB damaged. 
 
201909                                                                                                                                                                                                                        69 
 