Download Print this page

Midea M-Thermal Series Service Manual page 81

Advertisement

M‐Thermal Split
 
4.22 PP Troubleshooting 
Digital display output 
 
 
Description 
 Water side heat exchanger inlet temperature is higher than outlet temperature in heating mode. 
 M‐Thermal Split stops running. 
 Error code is displayed on hydronic box main PCB and user interface. 
 Hb indicates PP has displayed 3 times. 
 
Possible causes 
 Temperature sensor not connected properly or has malfunctioned. 
 4‐way valve is blocked or damaged. 
 Hydronic box main PCB damaged. 
 
80 
 
Midea CAC Confidential
 
   
201909 