Midea M-Thermal Series Service Manual page 79

Advertisement

M‐Thermal Split
 
4.21 Pd Troubleshooting 
Digital display output 
 
 
Description 
 High  temperature  protection  of  air  side  heat  exchanger  refrigerant  outlet  in  cooling  mode.  When  the  air  side  heat 
exchanger  refrigerant  outlet  temperature  is  higher  than  62°C  for  more  than  3  seconds,  the  system  displays  Pd 
protection  and  M‐Thermal  Split  stops  running.  When  the  air  side  heat  exchanger  refrigerant  outlet  temperature 
returns drops below 52°C, Pd is removed and normal operation resumes. 
 M‐Thermal Split stops running. 
 Error code is displayed on outdoor unit main PCB and user interface. 
 
Possible causes 
 Temperature sensor not connected properly or has malfunctioned. 
 Poor condenser heat exchange. 
 Fan motor damaged. 
 Hydronic box main PCB damaged. 
 