Download Print this page

Midea M-Thermal Series Service Manual page 55

Advertisement

M‐Thermal Split
 
Procedure 
 
Power supply for the main control board 
and transformer is abnormal
The transformer of hydronic unit is 
There is a source of electromagnetic 
radiation near the unit, such as 
high‐frequency transmitter or other high 
strength radiation device 
Communication wires P Q E between 
main control board of outdoor unit and 
hydraulic module have short circuited, 
disconnected or misconnected 
Replace outdoor unit main PCB and 
hydronic box main PCB in turn 
Notes:   
1.
Measure the voltages of transformer input port and out port. The input voltage of transformer is 220V AC, output voltage of transformer is 13.5V AC. If any 
voltages is abnormal, the power supply for the main control board of hydraulic module and transformer will be abnormal.   
2.
Measure the voltages of transformer output port ports. If the voltages are not normal, the transformer has malfunctioned. 
 
54 
H0 
     
1
 
    No 
2
malfunctioned
 
    No 
    No 
    No 
 
Midea CAC Confidential
 
 
 
Yes 
Provide normal power supply 
 
Yes 
Replace the transformer 
 
Yes 
Remove the source of interference 
 
Yes 
Reconnect the communication wires 
 
 
 
 
 
 
 
 
 
 
 
 
   
201909 