M‐Thermal Split
 
Situation  2:  L1  or  L2  error  appears  after  the  compressor  has  been  running  for  a  period  of  time  and  the  compressor 
speed is over 20rps 
 
Relay on outdoor unit main PCB is open 
Replace the inverter module
 
Notes:   
1.
If the fan motor is running and the DC voltage between terminals P and N on inverter module declined, Relay on the main control board ofoutdoor 
 
unit is open.
2.
When replacing an inverter module, a layer of thermally conductive silica gel should be painted on IPM module (on the reverse side of the inverter module 
PCB). Refer to Figure 4‐4.1.
   
 
 
 
 
 
 
 
 
 
 
 
 
 
relay 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
76 
L1 /L2 
     
    No 
2
 
 
 
Midea CAC Confidential
 
 
 
Yes 
Replace the outdoor unit main PCB 
 
 
 
 
 
 
   
201909 