4.7 F1 Troubleshooting 
Digital display output 
                       
 
Description 
 Low DC generatrix voltage. 
 M‐Thermal Split stops running. 
 Error code is displayed on hydronic system main PCB and user interface. 
 
Possible causes 
 The DC generatrix voltage is too low. 
 
Procedure 
 
F1 
 
Power supply is abnormal. 
        No 
LED on the Inverter 
Modules is lighting  
        No 
The input power of 
inverter module is 
abnormal  
        No 
The invert module is 
damaged, change it.  
 
 
 
 
 
 
 
 
 
 
 
 
 
201909                                                                                                                                                                                                                        51 
 
 
 
 
 
Yes 
Provide normal power 
 
 
Yes 
Voltage of PN is 380V. 
 
 
The main board is 
Yes 
damaged, change it. 
 
 
 
 
Midea CAC Confidential
  M‐Thermal Split
 
 
 
 
 
 
 
 
Yes 
Check the main board. 
 
 
 
 
 
 
 
 
 