M‐Thermal Split
 
Situation 3: L0 or L4 error appears after the compressor has been running for a period of time and the compressor 
speed is over 60rps 
 
Inverter module has overheated 
Inverter module is over‐current
Replace the inverter module
Notes:   
1.
Refer to Figure 4‐4.1. 
2.
Use  clip‐on  ammeter  to  measure  the  compressor  current,  if  the  current  is  normal  indicates  the  inverter  module  is  failed,  if  the  current  is  abnormal 
indicates the compressor is failed. 
3.
When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the PFC and IPM modules (on the reverse side of the 
inverter module PCB). Refer to Figure 4‐4.1.
 
Situation 4: L0 error appears occasionally/irregularly 
 
The outdoor unit ventilation is not good 
 
 
74 
L0 / L4 
     
    No 
2
 
    No 
3
 
 
L0 
     
 
Midea CAC Confidential
 
 
 
Repaint the thermally conductie silica 
gel on the IPM module, IGBT, diode, 
Yes 
brigde rectifer  (on the reverse side of 
the inverter module PCB)
 
Yes 
Replace the compressor 
 
 
 
 
Yes 
Ensure enough space for unit ventilation
 
 
 
 
 
 
 
 
   
201909 