Procedure 
 
Communication wires X Y E have short 
circuited, disconnected or are 
Communication wires X Y E are not 
connected in a daisy chain 
Wires between hydronic box main PCB 
and electric control box communication 
terminals block are loose 
Interference from high voltage (220V or 
Communication wires are close to a 
source of electromagnetic radiation such 
as transformer or strong fluorescent lamp
Replacing electric control box 
communication terminals block resolves 
Replace hydronic box main PCB 
 
Notes:   
1.
Measure  the  resistance  among  X,  Y  and  E.  The  normal  resistance  between  P  and  Q  is  120Ω,  between  P  and  E  is  infinite,  between  Y  and  E  is  infinite. 
Communication wiring has polarity. Ensure that the X wire is connected to X terminals and the Y wire is connected to Y terminals.   
201909                                                                                                                                                                                                                        45 
E2 
     
1
misconnected
 
    No 
    No 
    No 
higher) wires 
    No 
    No 
the error 
    No 
Midea CAC Confidential
 
 
 
Yes 
Reconnect the communication wires 
 
Connect the communication wires in a 
Yes 
daisy chain 
 
Yes 
Ensure the wires are connected properly
 
Ensure the communication wires and 
Yes 
high voltage wires are separated 
 
Remove the source of interference, or 
Yes 
add additional shielding to the 
communication wires 
 
 
 
 