V6 VRF 50/60Hz

5 Normal Operation Control

5.1 Component Control during Normal Operation
Table 3-5.1: Component control during normal cooling operation
Component
Inverter compressor A
Inverter compressor B
DC fan motor A
DC fan motor B
Electronic expansion valve
A
Electronic expansion valve
B
Electronic expansion valve
C
Four-way valve
Solenoid valve (oil balance)
Solenoid
valve
(fast
defrosting (in heating) and
unloading (in cooling))
Solenoid
valve
(EXV
bypass)
Solenoid
valve
(indoor
units bypass)
Solenoid valve (inverter
compressor
A
vapor
injection)
Solenoid valve (inverter
compressor
B
vapor
injection)
Solenoid valve (inverter
compressor
B
pressure
balance)
38
Wiring
diagram
8-12HP
14-16HP
label
COMP(A)
COMP(B)
FANA
FANB
EXVA
EXVB
EXVC
ST1
SV4
SV5
SV6
SV7
SV8A
SV8B
SV9
18-28HP
30-32HP
Controlled according to load requirement
Controlled according to discharge pressure
Position (steps) from 0 (fully closed) to 480 (fully
open),
temperature
Position (steps) from 0 (fully closed) to 480 (fully
open),
different between plate heat exchanger inlet and
outlet
Off
Open regularly
Controlled according to ambient temperature,
discharge
compressor running frequency and discharge
superheat
Controlled according to discharge pressure and
discharge temperature
Controlled according to load requirement
Controlled according to inverter compressor A
on/off
Controlled according to inverter compressor B
on/off
Open before compressor B startup and close after
compressor B running for 15 seconds. Open after
compressor B stop 10 seconds and keep open 60
seconds.
Control functions and states
controlled
according
to
controlled
according
to
pressure,
discharge
discharge
temperature
temperature,