Procedure 
 
High pressure switch connection or 
pressure sensor connection on outdoor 
unit main PCB is loose
Pressure sensor has short‐circuited or 
The high pressure side is blocked, caused 
by crushed or bent pipe or blocked EXV
The heat exchange is poor
The water flow rate is not sufficient in 
Replace outdoor main PCB 
 
Notes:   
1.
High pressure switch connection is port CN13 on the main control board of outdoor unit (labeled 10 in Figure 4‐2.2 in Part4, 2.3 "Main PCBs for Refrigerant 
System, Inverter Module". Pressure sensor connectin is port CN4 on the main control board of outdoor unit (labeled 15 in Figure 4‐2.2 in Part4, 2.3 "Main 
PCBs for Refrigerant System, Inverter Module" 
2.
Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor 
has failed. 
3.
High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to 
be lower than normal. 
4.
In heating mode check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages. In cooling mode check air side 
heat exchanger, fan(s) and air outlets for dirt/blockages. 
5.
Check  water  pressure  on  the  manometer.  If  the  water  pressure  is  not  >  1  bar,  water  flow  is  insufficient.  Refer  to  Figure  2‐1.6  and  2‐1.7  in  Part  2,  1.2 
"Hydronic Box Layout". 
 
201909                                                                                                                                                                                                                        63 
P1 
     
1
 
    No 
2
failed
 
    No 
    No 
4
 
    No 
5
cooling mode
 
    No 
 
Midea CAC Confidential
 
 
 
Ensure the pressure switch is connected 
Yes 
 
Yes 
Replace the pressure sensor 
 
Yes 
Inspect the system and fix the error 
3
 
Yes 
Inspect the system and fix the error 
 
Inspect the water system and fix the 
Yes 
 
 
  M‐Thermal Split
 
 
properly 
 
 
 
 
error 
 
 
 