M‐Thermal Split
 
Table 4‐3.1: Error code table (continued)
H8 
47 
Pressure sensor error 
H9 
48 
Circuit 2 water outlet temperature sensor error 
Water  side  heat  exchanger  water  outlet 
HA 
49 
temperature sensor error 
HF 
54 
Refrigerant system EEPROM error 
P0, 
20 
Low pressure protection 
HP 
57 
P1 
21 
High pressure protection 
P3 
23 
Compressor current protection 
P4 
24 
Discharge temperature protection 
High temperature difference between water side 
P5 
25 
heat  exchanger  water  inlet  and  water  outlet 
temperatures protection 
P6 
26 
Inverter module protection 
H4 
43 
L0 
‐ 
Inverter module protection 
 
L1 
DC bus low voltage protection 
 
L2 
DC bus high voltage protection 
 
L4 
MCE error 
 
L5 
Zero speed protection 
 
L7 
Phase sequence error 
Compressor  frequency  variation  greater  than 
 
L8 
15Hz within one second protection 
Actual  compressor  frequency  differs  from  target 
 
L9 
frequency by more than 15Hz protection 
Pb 
31 
Water side heat exchanger anti‐freeze 
High temperature protection of refrigerant outlet 
Pd 
33 
temperature of condenser in cooling mode 
PP 
38 
Water  side  heat  exchanger  inlet  temperature  is 
Hb 
50 
higher than outlet temperature in heating mode 
Notes: 
1.
When the error code appears, the error code corresponding to the serial number can be obtained through the H1H2 port by using the host 
computer to query the wired controller register. 
2.
Sensor names in this service manual referring to refrigerant flow is named according refrigerant flow during cooling operation refer to Part 2, 3 
"Refrigerant Flow Diagrams". 
 
 
40 
 
 
Midea CAC Confidential
 
User  interface  and  outdoor 
unit main PCB 
User  interface  and  hydronic 
box main PCB 
User  interface  and  hydronic 
box main PCB 
User 
interface 
refrigerant system main PCB 
User 
interface 
refrigerant system main PCB 
User 
interface 
refrigerant system main PCB 
User  interface  and  outdoor 
unit main PCB 
User  interface  and  outdoor 
unit main PCB 
User  interface  and  hydronic 
box main PCB 
User interface 
 
Outdoor unit main PCB
 
Outdoor unit main PCB
 
Outdoor unit main PCB
 
Outdoor unit main PCB
 
Outdoor unit main PCB
 
Outdoor unit main PCB
Outdoor unit main PCB 
Outdoor unit main PCB 
Hydronic box main PCB 
User  interface  and  outdoor 
unit main PCB 
User  interface  and  hydronic 
box main PCB 
 
Sensor T1B 
Sensor Tw_out 
and 
 
and 
 
and 
 
 
 
 
Displayed  on  user  interface 
when  any  of  L0,  L1,  L2,  L4, 
L5, L7, L8 or L9 occur 
 
 
 
 
 
 
 
 
 
 
 
   
201909 