4.19 P6 Troubleshooting for single‐phase models 
Digital display output 
 
 
Description 
 Inverter module protection. 
 M‐Thermal Split stops running. 
 Error code P6 is displayed on the user interface. Specific error code L0, L1, L2, L4, L5, L7, L8 or L9 is displayed on the 
outdoor unit main PCB. 
 
Possible causes 
 Inverter module protection. 
 DC bus low or high voltage protection. 
 MCE error. 
 Zero speed protection. 
 Phase sequence error. 
 Excessive compressor frequency variation. 
 Actual compressor frequency differs from target frequency. 
 
Specific error codes for P6 inverter module protection 
If a P6 error code is displayed on the user interface, one of the following specific error codes is displayed on the outdoor 
unit main PCB: L0, L1, L2, L4, L5, L7, L8, L9. Refer to Table 4‐4.1. 
 
Table 4‐4.1: Specific error codes for error P6
Specific error code 
L0 
L1 
L2 
L4 
L5 
L7 
L8 
L9 
 
The specific error codes can also be obtained from the LED indicators LED1/LED2 on the inverter module. Refer to Figure 
4‐4.2 and Figure 4‐2.4 or 4‐2.6 in Part 4, 2.1 "Outdoor Unit PCBs".   
 
201909                                                                                                                                                                                                                        71 
 
Inverter module protection 
DC bus low voltage protection 
DC bus high voltage protection 
MCE error 
Zero speed protection 
Phase sequence error 
Compressor frequency variation greater than 15Hz within one second protection 
Actual compressor frequency differs from target frequency by more than 15Hz protection
 