L1/L2 troubleshooting 
The normal DC voltage between terminals P and N on inverter module is 310V in standby and 380V when the fan motor is 
running. If the voltage is lower or higher than the normal voltage, the unit displays an L1 or L2 error. 
 
Figure 4‐4.2: Inverter module terminals 
                                                                                                       
 
Situation 1: L1 or L2 error appears immediately after the outdoor unit is powered‐on 
 
Power supply is abnormal 
Replace the inverter module
 
Notes:   
1.
When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module, IGBT, diode, brigde rectifer (on the 
reverse side of the inverter module PCB). Refer to Figure 4‐4.1.
 
 
 
 
 
 
 
 
 
 
 
201909                                                                                                                                                                                                                        75 
L1 / L2 
     
    No 
1
 
Midea CAC Confidential
 
U          V          W        N 
 
 
Re‐start the unit once the power supply 
Yes 
has returned to normal 
 
 
 
 
 
  M‐Thermal Split
 
 
 
 
 
 