M‐Thermal Split
 
4.16 P3 Troubleshooting 
Digital display output 
 
 
Description 
 Compressor current protection. 
 When the compressor current rises above the protection value (4/6kW models 18A, 8/10kW model 19A), the system 
displays  P3  protection  and  M‐Thermal  Split  stops  running.  When  the  current  returns  to  the  normal  range,  P3  is 
removed and normal operation resumes. 
 Error code is displayed on refrigerant system main PCB and user interface. 
 
Possible causes 
 Poor condenser heat exchange. 
 High pressure side blockage. 
 Inverter module damaged.   
 Compressor damaged. 
 Outdoor unit main PCB damaged. 
 
64 
 
 
Midea CAC Confidential
   
201909 