M‐Thermal Split
 
4.17 P4 Troubleshooting 
Digital display output 
 
 
Description 
 Discharge temperature protection. 
 When  the  compressor  the  discharge  temperature  rises  above  115°C,  the  system  displays  P4  protection  and 
M‐Thermal  Split  stops  running.  When  the  discharge  temperature  falls  below  90°C,  P4  is  removed  and  normal 
operation resumes. 
 Error code is displayed on refrigerant system main PCB and user interface. 
 
Possible causes 
 Temperature sensor error 
 High pressure side blockage. 
 Poor condenser heat exchange. 
 Outdoor unit main PCB damaged. 
 