Procedure 
 
Water flow switch connection on 
hydronic box main PCB is loose
Water flow is insufficient
Water flow switch is damaged 
Internal circulator pump can't work 
Replace hydronic box main PCB 
 
Notes:   
1.
Water flow switch connection is port CN8 on the main PCB for hydronic box (labeled 6 in Figure 4‐2.1 in Part4, 2.2 "Main PCB for Hydronic System").   
2.
Check water pressure on the manometer. If the water pressure is not > 1 bar, water flow is insufficient. Refer to Figure 2‐1.6 in Part 2, 1 "Hydronic Box 
Layout". 
3.
Revolve the pump shaft reversely around the clock, check the wire in the pump. 
 
 
 
201909                                                                                                                                                                                                                        43 
E0 / E8 
     
1
 
    No 
2
 
    No 
    No 
No   
 
 
Midea CAC Confidential
 
 
 
Yes 
Ensure the switch is connected properly 
 
Check the water piping and valves. Make 
sure the water piping is clean, there is no 
air in the water piping and all valves are 
Yes 
open. If the internal circulator pump is 
not already set to the highest speed, 
increase its speed. 
 
Yes 
Replace the water flow switch 
 
Yes 
Turn off the power, check the pump 
step 1, revolve the pump shaft reversely 
 
around the clock by hand, if can't 
revolve, replace the pump     
step 2, check the wire in the pump. Once 
 
that is done, the pump still can't work, 
replace the pump. 
  M‐Thermal Split
 
 
 
 
 
 