2 Piping Diagrams 
2.1 Outdoor Unit Piping   
MHA‐V4W/D2N8 / MHA‐V6W/D2N8 / MHA‐V8W/D2N8 / MHA‐V10W/D2N8 
Figure 2‐2.1: MHA‐V4(6,8,10)W/D2N8 piping diagram
 
Legend 
2.1 
2.2 
2.3 
2.4 
 
Key components: 
1. Electronic expansion valve (EXV): 
Controls refrigerant flow and reduces refrigerant pressure. 
2. Four‐way valve:   
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the air side heat 
exchanger functions as a condenser and water side heat exchanger functions as an evaporator; when open, the air 
side heat exchanger functions as an evaporator and water side heat exchanger function as a condenser. 
3. High and low pressure switches:   
Regulate refrigerant system pressure. When refrigerant system pressure rises above the upper limit or falls below the 
lower limit, the high or low pressure switches turn off, stopping the compressor.   
4. Separator:   
Separates liquid refrigerant from gas refrigerant to protect compressor from liquid hammering. 
 
201909                                                                                                                                                                                                                      11 
 
Compressor 
Discharge pipe temperature sensor 
Outdoor ambient temperature sensor
Air side heat exchanger refrigerant outlet temperature sensor
Suction pipe temperature sensor 
4‐way valve 
Air side heat exchanger 
Distributor 
Filter 
 
Midea CAC Confidential
 
Electronic expansion valve 
Stop valve (liquid side) 
9
Stop valve (gas side) 
10
Pressure sensor 
11 
Separator 
12.1
Low pressure switch 
12.2
High pressure switch 
13 
Capillary 
14 
Solenoid valve 
  M‐Thermal Split
 