Procedure 
 
The condenser heat exchange is poor
The high pressure side is blocked, caused 
by crushed or bent pipe or blocked EXV
Inverter module has short‐circuited
Compressor has malfunctioned
Replace outdoor main PCB 
 
Notes:   
1.
In heating mode check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages. In cooling mode check air side 
heat exchanger, fan and air outlets for dirt/blockages. 
2.
High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to 
be lower than normal. 
3.
Set a multi‐meter to buzzer mode and test any two terminals of P N and U V W of the inverter module. If the buzzer sounds, the inverter module has 
short‐circuited. 
4.
The normal resistances of the inverter compressor are 0.7‐1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances 
differ from these specifications, the compressor has malfunctioned. 
 
201909                                                                                                                                                                                                                        65 
P3 
    No 
1
 
    No 
2
    No 
3
 
    No 
4
 
    No 
 
Midea CAC Confidential
 
 
 
Yes 
Inspect the system and fix the error 
 
Yes 
Inspect the system and fix the error 
 
Yes 
Replace the inverter module 
 
Yes 
Replace the compressor 
 
 