Removing the PWR250-80 DC Power Supply

This section contains the procedure for removing the PWR250-80 DC
power supply.
Warning
As a safety precaution, install a circuit breaker with a minimum value
of 15 Amps between the equipment and the DC power source.
E9
Warning
Always connect the wires to the LAN equipment first before
connecting them to the circuit breaker. Do not work with HOT feeds
to avoid the danger of physical injury from electrical shock. Always
verify that the circuit breaker is in the OFF position before
connecting the wires to the circuit breaker.
Warning
For centralized DC power connection, install only in a restricted
access area.
Warning
This equipment must be installed in a Restricted Access location. 
E45
Note
A tray cable is required to connect the power source if the unit is
powered by centralized DC power. The tray cable must be a UL
listed Type TC tray cable and rated at 600 V and 90 degrees C, with
three conductors, minimum 14 AWG.
Perform the following procedure to the PWR250-80 DC Power Supply.
1. Power off the DC circuit to which the switch is connected.
2. Verify that the On/Off switch on the power supply is in the Off position.
Refer to Figure 85.
x530DP Series Installation Guide for Stand-alone Switches
E23
E9
E24
205