Figure 54. Dc Terminal Block On The Dc At-Pwr250 Power Supply Module; Figure 55. Stripped Wire - Allied Telesis 48Ts/X Installation Manual

X610 series layer 3 stackable gigabit ethernet switches
Table of Contents

Advertisement

Chapter 4: Cabling the Network Ports
96
A
A
+48 VDC Positive
Terminal
Figure 54. DC Terminal Block on the DC AT-PWR250 Power Supply
4. With a 14-gauge wire-stripping tool, strip the three wires in the tray
cable coming from the DC input power source to 8mm ± 1mm (0.31 in.,
± 0.039 in.), as shown in Figure 55 on page 96.
Warning
Do not strip more than the recommended amount of wire. Stripping
more than the recommended amount can create a safety hazard by
leaving exposed wire on the terminal block after installation.
8mm ±1mm
(0.31in. ±0.039in.)
5. Insert the power supply ground wire into the middle connector of the
DC terminal and tighten the connection with a flathead screwdriver, as
shown in Figure 56 on page 97.
40-60VDC
DC OUT
6A
FAULT
+
-
ON
OFF
Ground
-48 VDC Negative
Terminal
Module

Figure 55. Stripped Wire

2205
Terminal
E10

Advertisement

Table of Contents
loading

Table of Contents