Download Print this page

System With A Connection Of System Controller To Centralized Control Transmission Line - Mitsubishi Electric PURY-M200YNW-A1 Service Handbook

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[2-7 Example System with an MA Remote Controller ]
2-7-4
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
An example of a system in which a system controller is connected to the transmission cable for the centralized control system
and the power is supplied from the outdoor unit
Move the male connector
from CN41 to CN40.
SW5-1 OFF
OC
51
TB3
M1M2
TB7
M1M2
S
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OC
54
TB3
M1M2
TB7
M1M2
S
System controller
A B S
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a group
of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units (not required if power to the
transmission line for centralized control is supplied from a controller
with a power supply function, such as GB-50ADA).
5)
Short-circuit the shield terminal (S terminal) and the earth terminal (
) on the terminal block for transmission line for centralized control
(TB7) on the outdoor unit whose power jumper connector is mated
with CN40.
6)
When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
When the W/WP/WL200 and
W/WP/WL250 models are not includ-
ed in the connected indoor units
When the W/WP/WL200 and
W/WP/WL250 models are included in
the connected indoor units
BS_02_L
Group
HB
IC
52
01
TB3
TB5
TB15
M1M2
S
M1M2
S
1 2
To be connected
A
B
1
2
MA
L22
Group
HB
IC
55
04
TB3
TB5
TB15
M1M2
S
M1M2
S
1 2
To be left
unconnected
A
B
1
2
MA
m3
Note1
Number of transmission booster
(sold separately) required
1 unit
2 units
25 - 50 units
-
19 - 37 units
38 - 50 units
Interlock operation with
the ventilation unit
L12
Group
Group
IC
IC
02
03
TB5
TB15
TB5
TB15
M1M2
M1M2
S
1 2
S
1 2
A
B
A
B
1
2
1
2
MA
MA
Group
IC
IC
05
06
TB5
TB15
TB5
TB15
M1M2
S
1 2
M1M2
M1M2
S
1 2
A
B
1
2
MA
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 220 - 240V.
The left table shows the number of transmission boosters that is re-
quired by the system with four HBCs. For each HBC added or sub-
tracted, subtract or add two indoor units.
Refer to the DATABOOK for further information about how many
booster units are required for a given system.
7)
When a power supply unit is connected to the transmission line for
centralized control, leave the power jumper connector on CN41 as it
is (factory setting).
(3) Maximum allowable length
1)
Indoor/outdoor transmission line
Same as 2-7-3
2)
Transmission line for centralized control
L31+L32
200m [656ft]
3)
MA remote controller wiring
Same as 2-7-1
4)
Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L32+L31+L12
1000 m [3280ft] (500 m [1640ft])
L32+L22
1000 m [3280ft] (500 m [1640ft])
L12+L31+L22
1000 m [3280ft] (500 m [1640ft])
*1 If a given system includes one or more unit or remote controller
that does not support the maximum allowable cable distance of
1000 m [3280 ft], the maximum allowable cable distance in the
system will be 500 m [1640 ft]. Refer to the latest catalog for in-
formation on which units and remote controllers support the max-
imum allowable cable distance of 1000 m [3280 ft].
LC
07
TB5
M1M2
S
LC
08
TB5
S
*1
*1
*1
17
chapter 2 -

Hide quick links:

Advertisement

loading