Download Print this page

Checking The Inverter For Damage During Compressor Operation; Checking The Converter For Damage During Compressor Operation - Mitsubishi Electric PURY-M200YNW-A1 Service Handbook

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[8-10 Troubleshooting Inverter Problems ]
8-10-5

Checking the Inverter for Damage during Compressor Operation

Items to be checked
Put the outdoor unit into opera-
tion.
Check the inverter output volt-
age (at the compressor terminal)
after the inverter output frequen-
cy has stabilized.
<INV35Y, 42Y>
44
- chapter 8
Phenomena
1)
Overcurrent-related problems occur im-
mediately after compressor startup.
Error code : 4250
Detail code : 101, 102, 106, 107
2)
There is a voltage imbalance between
the wires after the inverter output voltage
is stabilized.
Greater than the larger of the following
values: imbalance of 5% or 5V
Remedy
a.
Check items [8-10-2 Checking the
Inverter Board Error Detection Cir-
cuit] through [8-10-4 Checking the
Inverter for Damage at No-Load]
for problems.
b.
Check that high and low pressures
are balanced.
c.
Check that no liquid refrigerant is
present in the compressor and that
there is no liquid backflow.
→Go to "d." when the problem per-
sists after compressor startup was
repeated several times.
d.
Check that there is a pressure dif-
ference between high and low
pressures after compressor start-
up.
→Check the high pressure with
LED monitor for changes.
Replace the compressor if there is
no pressure difference. (the com-
pressor may be locked.)
Replace the INV board if there is a volt-
age imbalance.
BS_08_L

Hide quick links:

Advertisement

loading