Outdoor Units Stop At Irregular Times - Mitsubishi Electric PURY-M200YNW-A1 Service Handbook

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[8-3 Refrigerant Control Problems ]
8-3-3

Outdoor Units Stop at Irregular Times.

1. Phenomena
Outdoor unit stops at times during operation.
2. Cause, check method and remedy
The first stop is not considered as an error, as the
unit turns to anti-restart mode for 3 minutes as a pre-
liminary error.
Error mode
1)
Abnormal high pressure
2)
Abnormal discharge air temperature
3)
Heatsink thermistor failure
4)
Thermistor failure
5)
Pressure sensor failure
6)
Over-current break
7)
Refrigerant overcharge
Note1:
Frost prevention tripping only under cooling mode
may be considered in addition to the above. (Freeze
protection is detected by one or all indoor units.)
Note2:
Even the second stop is not considered as an error
when some specified errors occur. (eg. The third
stop is considered as an error when the thermistor
error occurs.)
14
- chapter 8
Cause
Check method and remedy
(1)
Check the mode operated in the past by displaying
preliminary error history on LED display with SW4.
(2)
Reoperate the unit to find the mode that stops the
unit by displaying preliminary error history on LED
display with SW4.
Refer to the reference page for each error mode.
*Display the indoor piping temperature with SW4 to
check whether the freeze proof operation runs
properly, and check the temperature.
BS_08_L