[10-2 LED Status Indicators (HBC) ]
10-2-2
Initial LED Display (HBC)
From power on until the completion of initial settings, the following information will be displayed on the monitor screen.
(Displays No. 1 through No. 4 in order repeatedly.)
No
Item
Software version
1
Refrigerant type
2
Model and capacity
3
Communication address
4
Only item No. 1 "Software Version" appears on the display if there is a wiring failure between the control board and the trans-
mission line power supply board or if the circuit board has failed.
If nothing appears on the display after the power is turned on, 4130 error may be occurring.
Take the procedure described in section [7-6-12 Error Code [4130]].
BS_10_M
Display
[1100] : Version 11.00
[ 32] : R32
[Hb-3] : WM350F
[Hb-4] : WM500F
[ 52] : Address 52
Remarks
[HS08] : WM108V
[HS16] : WM1016V
chapter 10 -