[1-2 Handling and Characteristics of Piping Materials, Refrigerant, and Refrigerant Oil ]
C: Create an appropriate ventilation open area.
Good
Longitudinal
direction
Width of an opening
≥ 0.9 m
NG
13. Installation restrictions for HBC
Observe the following restrictions that apply to the installation of HBC.
[Restrictions for HBC installation]
• Do not place an ignition source in a space where a HBC is installed or adjacent spaces not shielded by
firewalls.
Examples: Lighters, combustion heaters, combustion boilers, and combustion cookers
• Figure 2 shows the minimum floor areas required for given amounts of refrigerant in various refrigerant
systems. Make sure the installation conditions meet the requirements shown in the figure. Take appropriate
safety measures in accordance with the instructions provided in Figure 2.
• All of the above-mentioned restrictions apply not only to new installations but also to relocations and layout
changes.
Figure 2
In addition to what is listed below, floor-standing units will require an agitator.
12 -
chapter 1
Height of an opening
≥ 0.15 m
Height from the ground to
an opening ≥ 0.125 m
(Example: basement)
80
NG (ISO 5149)
70
60
50
At least two safety
measures are
40
required.
30
20
10
0
0
50
100 150 200 250 300 350 400 450 500 550 600 650
Room volume [m
Opening:
• Must occupy 80% of the
longitudinal side of a space.
• Must have an opening ratio of
75% or higher.
(Example: space with a louver)
At least one safety
measure is required.
Construction guidance
3
]
BS_01_L