[2-1 System Configurations ]

2-1

System Configurations

2 Restrictions
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
Outdoor units
HBC
M200YNW-A1
M250YNW-A1
CMB-
WM350F-AA
M300YNW-A1
M350YNW-A1
M400YNW-A1
CMB-
M450YNW-A1
WM500F-AA
M500YNW-A1
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
3) Only either P**Y-W model indoor units (equipped with a flow control valve) or P**Y-WP/WL model indoor units (without a flow
control valve) can be connected to the HBC. (Combining different models of indoor units will cause a connection error.)
4) The following models of indoor units can be used as indoor units equipped with a flow control valve when used with the op-
tional valve kit (PAC-SK04VK-E).
<Applicable indoor units>
P**Y-WL**
* The optional valve kit (PAC-SK04VK-E) cannot be installed on P**Y-WP** models.
(2) High COP combinations
Outdoor units
HBC
EM200YNW-A1
EM250YNW-A1
CMB-
WM350F-AA
EM300YNW-A1
EM350YNW-A1
EM400YNW-A1
CMB-
EM450YNW-A1
WM500F-AA
EM500YNW-A1
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
3) Only either P**Y-W model indoor units (equipped with a flow control valve) or P**Y-WP/WL model indoor units (without a flow
control valve) can be connected to the HBC. (Combining different models of indoor units will cause a connection error.)
4) The following models of indoor units can be used as indoor units equipped with a flow control valve when used with the op-
tional valve kit (PAC-SK04VK-E).
<Applicable indoor units>
P**Y-WL**
* The optional valve kit (PAC-SK04VK-E) cannot be installed on P**Y-WP** models.
BS_02_L
Number of
connectable
Sub-HBC
HBC
1
CMB-
WM108V-BB
CMB-
WM1016V-BB
1
Number of
connectable
Sub-HBC
HBC
1
CMB-
WM108V-BB
CMB-
WM1016V-BB
1
Maximum
Maximum total
number of
capacity of
connectable
connectable
Sub-HBC
indoor units
100 - 300
125 - 375
150 - 450
3
175 - 525
200 - 600
225 - 675
250 - 750
Maximum
Maximum total
number of
capacity of
connectable
connectable
Sub-HBC
indoor units
100 - 300
125 - 375
150 - 450
3
175 - 525
200 - 600
225 - 675
250 - 750
Maximum
Types of
number of
connectable
connectable
indoor units
indoor units
30
W/WP/WL10 -
W/WP/WL125
37
models
R32 series
45
indoor units
50
50
50
50
Maximum
Types of
number of
connectable
connectable
indoor units
indoor units
30
W/WP/WL10 -
W/WP/WL125
37
models
R32 series indoor
45
units
50
50
50
50
chapter 2 -
1