System With A Connection Of System Controller To Centralized Control Transmission Line - Mitsubishi Electric PURY-P200YLM-A(1) Service Handbook

Table of Contents

Advertisement

[2-7 Example System with an MA Remote Controller ]
2-7-4
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
An example of a system in which a system controller is connected to the transmission cable for the centralized control system
and the power is supplied from the outdoor unit
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
52
TB3
M1M2
TB7
M1M2
S
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OS
56
TB3
M1M2
TB7
M1M2
S
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be connect-
ed to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a group of
indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that are con-
nected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units (not required if power to the trans-
mission line for centralized control is supplied from a controller with a
power supply function, such as GB-50ADA).
5)
Short-circuit the shield terminal (S terminal) and the earth terminal (
on the terminal block for transmission line for centralized control (TB7) on
the outdoor unit whose power jumper connector is mated with CN40.
6)
When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
When the P200 and P250 models are
not included in the connected indoor
units
When the P200 and P250 models are
included in the connected indoor
units
HWE1314A
L11
Move the male connector
from CN41 to CN40.
SW5-1 OFF
OC
BC
51
53
TB3
TB02
M1M2
M1M2
S
TB7
M1M2
S
To be left
unconnected
To be connected
L21
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
OC
BC
55
57
TB3
TB02
M1M2
M1M2
S
TB7
To be left
M1M2
S
unconnected
To be left
unconnected
Note1
System controller
A B S
Number of transmission booster
(sold separately) required
1 unit
2 units
27 - 50 units
-
21 - 39 units
40 - 50 units
L12
Group
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1M2
S
1 2
M1M2
S
1 2
A
B
A
B
1
2
1
2
MA
MA
L22
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1M2
S
1 2
M1M2
S
1 2
A
B
1
2
MA
m3
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 220 - 240V.
The left table shows the number of transmission boosters
that is required by the system with three BC controllers. For
each BC controller that is subtracted from the above-men-
tioned system, two additional indoor units can be connected.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
7) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connec-
tor on CN41 as it is (factory setting).
(3) Maximum allowable length
)
1) Indoor/outdoor transmission line
Same as 2-7-3
2) Transmission line for centralized control
L31+L32(L21)
3) MA remote controller wiring
Same as 2-7-1
4) Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L32+L31+L12(L11)
L32+L22(L21)
L12(L11)+L31+L22(L21)
- 40 -
Interlock operation with
the ventilation unit
Group
LC
IC
03
07
TB5
TB15
TB5
M1M2
S
1 2
M1M2
S
A
B
1
2
MA
Group
LC
IC
08
06
TB5
TB5
TB15
M1M2
M1M2
S
S
1 2
A
B
1
2
MA
200m [656ft]
500m [1640ft]
500m [1640ft]
500m[1640ft]
GB