[5-2 Outdoor Unit Control ]
5-2-8
Outdoor Unit Fan Control
(1) Control method
Depending on the capacity required, the rotation speed of the outdoor fan is controlled by the inverter to keep a constant con-
densing temperature (outside temperature + 10°C [50°F]) during cooling operation and a constant evaporation temperature
(0°C [32°F] = 0.71 MPa [103 psi]) during heating operation.
(2) Control
Outdoor unit fan stops while the compressor is stopped (except in the presence of input from snow sensor).
The fan operates at full speed for 5 seconds after start-up.(Only when TH7<0°C [32°F])
The outdoor unit fan stops during defrost operation.
Both fans operate on the (E)M350, (E)M400, (E)M450, and (E)M500 models of outdoor units.
(3) Outdoor heat exchanger capacity control pattern
Outdoor fan rotation control is supported.
As the operation pattern number increases, the refrigerant bypassing the outdoor heat exchanger increases. As the operation
pattern number increases, the capacity difference becomes smaller between cooling operation and heating operation.
In each mode, the four-way valve and the expansion valve operate as shown in the table below. The expansion valve may
open or close during the refrigerant equalization control or the evaporation temperature control. See [5-2-9 Expansion valve
control (LEV2a, LEV2b, LEV2c, and LEV2d)]
Operation
Model
mode
(E)M200,
Cooling-only
(E)M250,
Cooling-main
(E)M300
models
Heating-only
Heating-main
Defrost
(E)M350,
Cooling-only
(E)M400,
Cooling-main
(E)M450
models
Heating-only
Heating-main
Defrost
(E)M500
Cooling-only
models
Cooling-main
Heating-only
Heating-main
Defrost
(4) Evaporation temperature control (Expansion valves LEV2a, LEV2b, LEV2c, and LEV2d)
LEV is controlled every 30 seconds so that the minimum temperature of the liquid refrigerant (TH12) of the Cooling-main heat
exchanger and of the bypass inlet (TH15) of the HBC are in a constant range during Heating-only or Heating-main operation.
18
- chapter 5
Four-way valve
Operation
patterns
21S4a
21S4b
1
OFF
OFF
2
OFF
ON
3
OFF
ON
4
OFF
ON
1
ON
ON
1
ON
ON
2
ON
ON
1
OFF
OFF
1
OFF
OFF
2
OFF
ON
3
OFF
ON
4
OFF
ON
1
ON
ON
1
ON
ON
2
ON
ON
1
OFF
OFF
1
OFF
OFF
2
OFF
ON
3
OFF
ON
4
OFF
ON
1
ON
ON
1
ON
ON
2
ON
ON
1
OFF
OFF
21S4c
LEV2a
LEV2b
-
3000
3000
-
3000
41
-
500
41
-
300
41
-
3000
3000
-
3000
3000
-
3000
3000
-
3000
3000
-
3000
3000
-
3000
41
-
3000
41
-
1000
41
-
3000
3000
-
3000
3000
-
3000
3000
-
3000
3000
OFF
3000
3000
ON
3000
41
ON
3000
41
ON
1000
41
ON
3000
3000
ON
3000
3000
ON
3000
3000
OFF
3000
3000
LEV
LEV2c
LEV2d
LEV4
-
41
*Injection
controlled
-
1000
-
3000
-
3000
-
41
-
41
-
1250
-
41
-
20
-
800
-
6000
-
6000
-
20
-
20
-
1000
-
20
3000
20
41
800
41
6000
41
6000
3000
20
3000
20
3000
1000
3000
20
BS_05_M

Hide quick links:

Advertisement

loading