[5-1 Dipswitch Functions and Factory Settings ]
7) Selectable with the function switches SW6-9 and SW6-10.
ON
SW6-9
OFF
Switch
SW4
1-10
SW6-10:
1:ON, 0:OFF
OFF
No.769
1000000011
No.817
1000110011
No.818
0100110011
No.832
0000001011
No.848
0000101011
No.876
0011011011
No.885
1010111011
No.886
0110111011
No.891
1101111011
No.896
0000000111
No.897
1000000111
No.900
0010000111
No.912
0000100111
No.913
1000100111
SW4
1-10
[0:OFF,
1:ON]
No.915
1100100111
(Note 1)
SW6-10:ON
No.916
0010100111
No.918
0110100111
No.921
1001100111
No.922
0101100111
No.933
1010010111
No.934
0110010111
No.935
1110010111
No.956
0111011110
No.958
0111110111
No.982
0110101111
No.997
1010011111
No.1006
0111011111
BS_05_M
ON
Self-diagnosis monitor display (round
type LED) No. 0 to 1023
SW4 function setting mode No. 0 to 1023
Function according to switch setting
Function
OFF (LED3 Unlit)
Self-diagnosis/operation
Refer to the following page(s). [10 LED Sta-
monitor
tus Indicators]
Test run mode: ON/OFF
Stops all ICs
Starts up drive recorder
Enabled
Data collection during an
Disabled
error
Cumulative compressor
Retained
operation time deletion
Continuous heating cycle
Disabled
function
High-pressure over-rise
SV2 is used.
backup setting
Fan speed setting at low
outside temperature heat-
Refer to Note 8).
ing
Smooth auto-shift startup
Disabled
mode
Clearance of error
OC
Retained (IC/OC)
history SW
High sensible heat opera-
Depends on the combined setting with No.
tion setting
900 (Note 7)
High sensible heat opera-
Depends on the combined setting with No.
tion setting
897 (Note 7)
Pump down function
Normal control
Forced defrost (Note 2)
Normal control
(E)P200, (E)P250:
Defrost start temperature
-10°C [14°F]
(Note 2)
(E)P300 - (E)P500:
-8°C [18°F]
Defrost end temperature
7°C [45°F]
(Note 2)
Changes the defrost timer
50 minutes
setting (Note 2)
Temperature unit display
°C
Refrigerant amount adjust-
Normal control
ment
Effective only when
TH7 ≤ 5 is true or the
Snow sensor setting
snow sensor contact
input is on.
Continuous fan op-
Snow sensor setting
eration (FAN=50%)
High heating power (at low
Effective
outside temperature)
SV2 control time setting af-
Always ON
ter recovery from defrost
Clear the history of com-
Retained
pleting initial control
Target evaporation tem-
Refer to Note 3).
perature setting
Depends on the combined setting with No.
Multiple-stage low-noise
1006 (Note 6)
setting
Depends on the combined setting with 997
(Note 7)
SW6-10
OFF
Self-diagnosis monitor display (7seg
LED) No. 1024 to 2047
Self-diagnosis monitor display (7seg
LED) No. 0 to 1023
Switch setting timing
ON (LED3 Lit)
Anytime after power on
Sends a test-run sig-
Anytime after power on
nal to all IC
Disabled
Anytime after power on
Enabled
Anytime after power on
Cleared
Anytime after power on (OFF → ON)
After being energized and while the compres-
Enabled
sor is stopped
After being energized and while the compres-
LEV9 is used.
sor is stopped
After being energized and while the compres-
sor is stopped
After being energized and while the compres-
sor is stopped
After being energized and while the compres-
Enabled
sor is stopped
Deleted (IC/OC)
Anytime after power on (OFF → ON)
Anytime after power on (OFF → ON)
Anytime after power on (OFF → ON)
Pump down opera-
After being energized and while the compres-
tion
sor is stopped
10 minutes after the completion of defrost op-
Forced defrost starts
eration (OFF →ON) or 10 minutes after com-
pressor start-up (OFF → ON)
-5°C [23°F]
Anytime after power on
12°C [54°F]
Anytime after power on
90 minutes
Anytime after power on (OFF →ON)
°F
Anytime after power on
Anytime after power on (except during initial
Refrigerant amount
startup/becomes ineffective 90 minutes after
adjust mode
compressor started up.)
Effective when TH7
Anytime after power on
≤ 5 is true
Intermittent fan op-
eration (100% for 5
Anytime after power on
minutes ↔ 0% for 30
minutes)
Ineffective
Anytime after power on
After being energized and while the compres-
5 minutes
sor is stopped
After being energized and while the compres-
Cleared
sor is stopped
* Effective only OFF to ON
Anytime after power on
After being energized and while the compres-
sor is stopped
After being energized and while the compres-
sor is stopped