Error Code [7101]

1. Error code definition
Capacity code setting error
2. Error definition and error detection method
Connection of incompatible (wrong capacity code) indoor unit or outdoor unit
3. Error source, cause, check method and remedy
After troubleshooting the error using the check methods and remedies shown below, turn the power back on.
Error source
Indoor unit
(1) The model name (capacity code) set by the
switch (SW2) is wrong.
*The capacity of the indoor unit can be con-
firmed by the self-diagnosis function (SW1
operation) of the outdoor unit.
Outdoor unit
(2) The model selection switches (SW5-3 - 5-8)
on the outdoor unit are set incorrectly.
M200 model
M250 model
M300 model
M350 model
M400 model
M450 model
M500 model
EM200 model
EM250 model
EM300 model
EM350 model
EM400 model
EM450 model
EM500 model
HBC
(3) The model name (capacity code) setting is
wrong.
Correct combinations of outdoor units and
HBCs.
82
- chapter 7
Cause
SW5
Model
3
4
5
6
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
OFF
OFF OFF
ON
ON
OFF OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
OFF
OFF OFF
ON
ON
OFF OFF
ON
Outdoor unit
HBC
(E)M200 model
(E)M250 model
WM350 model
(E)M300 model
(E)M350 model
(E)M400 model
(E)M450 model
WM500 model
(E)M500 model
Check method and remedy
1) Check the model name (capacity code) of the in-
door unit which has the error source address set
by the switch (SW2 on indoor unit board).
When the model name set by the switch is differ-
ent from that of the unit connected, turn off the
power source of the outdoor and the indoor units,
and change the setting of the capacity code.
Check the setting for the model selection switch
on the outdoor unit (Dipswitches SW5-3 - 5-8 on
the outdoor unit control board).
7
8
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Check the model selection switch of the outdoor
unit (Dip switches SW5-3 through 5-8) on the out-
door unit control board.
BS_07_M

Hide quick links:

Advertisement

loading