Example System With An Me Remote Controller; System With A Connection Of System Controller To Centralized Control Transmission Line - Mitsubishi Electric R410A Service Handbook

Hide thumbs Also See for R410A:
Table of Contents

Advertisement

[2-8 Example System with an ME Remote Controller ]

2-8

Example System with an ME Remote Controller

2-8-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
ON
OS2
53
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
ON
OS2
56
TB3
M1 M2
TB7
M1 M2
S
To be left
unconnected
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2)
No more than 3 ME remote controllers can be connected to a
group of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that
are connected to different outdoor units with each other.
4)
Replace the power jumper connector of the control board from
CN41 to CN40 on only one of the outdoor units.
5)
Provide an electrical path to ground for the S terminal on the ter-
minal block for centralized control on only one of the outdoor
units.
6)
A transmission booster must be connected to a system in which
the total number of connected indoor units exceeds 20.
7)
A transmission booster is required in a system to which more
than 16 indoor including one or more indoor units of the 72 mod-
el or above are connected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
8) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connec-
tor on CN41 as it is (factory setting).
HWE14080
L11
Move the male connector
Leave the male
from CN41 to CN40.
connector on
SW5-1 OFF ON
CN41 as it is.
Group
SW5-1 OFF
ON
OS1
OC
52
51
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be connected
L21
Leave the male
Leave the male
connector on
connector on
CN41 as it is.
CN41 as it is.
SW5-1 OFF
ON
SW5-1 OFF
ON
Group
OS1
OC
55
54
TB3
TB3
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
To be left
unconnected
To be left
unconnected
Note1
System controller
A B S
Interlock operation with
the ventilation unit
L12
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
A B
101
102
RC
RC
L22
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1 M2
S
1 2
M1 M2
S
1 2
A B
A B
154
104
RC
RC
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 208/230V.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-3
2) Transmission line for centralized control
Same as 2-7-4
3) M-NET remote controller wiring
Maximum overall line length
2
(0.3 to 1.25mm
[AWG22 to 16])
m1 10m [32ft]
m2+m3 10m [32ft]
If the standard-supplied cable must be extended, use a
cable with a diameter of 1.25mm
of the cable that exceeds 10m [32ft] must be included in
the maximum indoor-outdoor transmission line distance
described in 1).
*When connected to the terminal block on the Simple re-
mote controller, use cables that meet the following cable
size specifications: 0.75 - 1.25 mm
4) Maximum line distance via outdoor unit
2
(1.25 mm
[AWG16] min.)
Same as 2-7-4
- 40 -
Group
LC
IC
03
07
TB5
TB15
TB5
M1 M2
S
1 2
M1 M2
S
A B
103
RC
LC
IC
06
08
TB5
TB15
TB5
M1 M2
M1 M2
S
S
1 2
A B
106
RC
2
[AWG16]. The section
2
[AWG18-14].
GB