[8-13 Parts Replacement Instructions (Outdoor Unit) ]
(9) Remove the pipe cover and the damper, and cut the suction pipe where indicated in Figure 9.
(10) Remove the pipe covers, and then remove the braze. (See Figure 10.)
* Do not force the injection pipe to deform.
(11) Remove the compressor discharge pipe by cutting the pipe where indicated in Figure 11 or by removing the braze.
Cut the suction
pipe here.
Cut the compressor
discharge pipe here.
Figure 11
(12) Remove the four bolts holding the compressor down. (See Figure 12.)
The two bolts in the front are also holding down the metal sheets.
(13) Tilting the compressor will cause the refrigerant oil to leak. Seal the pipe where it was cut or removed at the brazed
section.
(14) After replacing the compressor, braze the pipes that were removed as they were.
In case of brazing the suction pipe, protect the surrounding components such as the control box, ACC, compressor cover,
and damper with a fire protection panel (e.g., recommended felt soaked in water), attach the supplied pipe,and perform
brazing. (See Figure 13.)
*Perform brazing, referring to "Notes on replacing refrigerant circuit parts (check valve block assemblies, four-way valves,
solenoid valves, and LEVs)" in 8-13-4.
(15) The recommended tightening torque for the compressor fixing bolts is 3.0 N·m. Fasten the bolts using a torque wrench or
other tool that can apply the specified torque.
(16) Re-place the compressor covers in the reverse order as they were removed.
*Hold the TH15 wiring in place with the bands to keep the wiring from coming in contact with insulation 2. (See Figures 3
and 7.)
Compressor fixing bolts
Compressor fixing
metal sheets and bolts
Figure 12
After replacing the compressor, set SW4 (832) and (958) to "ON" before conducting a test run.
After the test run has completed, set SW4 (832) and (958) to "OFF."
BS_08_L
Pipe cover
(ID: 43 mm; Length: 260 mm)
Damper and cable tie
(Length: 180 mm and 250 mm)
Figure 9
Area to be brazed
Remove the two
pipe covers.
* Save the pipe
covers for later
use.
Figure 10
Damper
ACC
Fire protection panel
(Recommended felt soaked in water etc.)
Control box
Attach the supplied pipe.
Compressor
Figure 13
Remove the braze here.
97