[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
7-6-24

Error Code [4240, 4245, 4246]

1. Error code definition
Overload protection
2. Error definition and error detection method
If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes during inverter operation.
Refer to the following page(s). [7-1 Error Code and Preliminary Error Code Lists]
3. Cause, check method and remedy
[Outdoor unit]
Cause
(1)
IPM contact failure
(2)
Air passage blockage
(3)
Power supply environment
(4)
Inverter, FAN board failure
(5)
Compressor failure
(6)
The model selection switches
(SW5-3 - 5-8) on the outdoor
unit are set incorrectly.
[HBC]
Cause
(1)
IPM contact failure
(2)
Power supply environment
(3)
Pump INV board failure
(4)
Pump failure
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
BS_07_M
Check method and remedy
Check the IPM and cooling plate for proper contact. (Remove the inverter board,
and check the IPM heatsink grease.)
Check that the heat sink cooling air passage is not blocked
Power supply voltage is 342 V or above.
Refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Check that the compressor has not overheated during operation.
→ Check the refrigerant circuit (oil return section).
Refer to the following page(s). [8-10-3 Checking the Compressor for Ground
Fault and Coil Resistance Problems]
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]]
Check method and remedy
Check the IPM and cooling plate for proper contact. (Remove the inverter board,
and check the IPM heatsink grease.)
Power supply voltage is 198 V or above.
Refer to the following page(s).
[8-10-12 Checking the Error-Detection Circuit on the Pump INV Board (Without
load)]
[8-10-13 Checking the Pump INV Board for Damage (Without load)]
[8-10-14 Checking the Pump INV Board for Damage (During pump operation)]
Check that the pump has not overheated during operation.
→ Check the refrigerant circuit (oil return section).
Refer to the following page(s).
[8-9-4 Water Pump Control]
[8-10-11 Checking the Pump Motor for Ground Fault and Coil Resistance Prob-
lems]